SC B 13 Three Dimensional Wound Core

SC B 13 Three Dimensional Wound Core

Product features of SC(B)13 type three dimensional wound core dry type transformer (compared with conventional superimposed core transformer) Low loss: three dimensional wound core dry type transformer has little seamless reluctance, close winding, high fill factor and light core weight....

Send InquiryChat Now

Product features of SC(B)13 type three dimensional wound core dry type transformer (compared with conventional superimposed core transformer)
Low loss: three dimensional wound core dry type transformer has little seamless reluctance, close winding,  high fill factor and light core weight. Compared with conventional laminated core dry type transformer,  no-load loss Po can reduce 18%~28%.  No-load current Io reduce 50%~60%. It has significant energy-saving effect and economical operation.
 
Low noise: noise level of three dimensional wound core dry type transformer was 5~10db lower than conventional laminated core dry type transformer, and 15~20 db lower than professional standard JB/T10088-2004 

Low partial discharge levels: Resin mixture use advanced foreign stirring method and vacuum film degassing, it will mix the mixture evenly, exclude bubble from compound, high and low voltage windings are all poured under vacuum pressure, resin insulation is fully wrapped, layers have complete permeability. Partial discharge quantity of products controlled under 5PC. Casting body has compact curing structure, it is flame retardant,  anti-explosive and will not pollute the environment.  

High mechanical strength: Three dimensional wound core use orbicular core section, anti-short circuit ability is better than oval section. Filled resin will lessen dilatation coefficient difference, cure shrinkage rate and innerstress, elevate curing hardness. Prefabricated forming strengthening material in epikote encapsulated layer will make mechanical strength much larger than pure epoxy resin, so the product can bear sudden short circuit without damage.   

SC(B)13 type three dimensional wound core dry type transformer main performance parameters:

Model Number

Rated capacity(KVA)

symbols in link groups

KV

open circuit loss(W)

load loss(W)

no-load current(%)

Short circuit resistance(%)

high pressure

tapping range

low tension

SC13-RL-30

30

Yyn0
     or
     Dyn11

10
     6.3
     6

±5%
     ±2×2.5%
     or
     +3×2.5%
     -1×2.5%

0.4

150

710

2.3

4.0

SC13-RL-50

50

215

1000

2.2

SC13-RL-80

80

295

1380

1.7

SC13-RL-100

100

320

1570

1.7

SC13-RL-125

125

375

1850

1.5

SCB13-RL-160

160

430

2130

1.5

SCB13-RL-200

200

495

2530

1.3

SCB13-RL-250

250

575

2760

1.3

SCB13-RL-315

315

705

3470

1.1

SCB13-RL-400

400

785

3990

1.1

SCB13-RL-500

500

930

4880

1.1

SCB13-RL-630

630

1070

5880

0.9

SCB13-RL-630

630

1040

5960

0.9

6.0

SCB13-RL-800

800

1215

6960

0.9

SCB13-RL-1000

1000

1415

8130

0.9

SCB13-RL-1250

1250

1670

9690

0.9

SCB13-RL-1600

1600

1960

11730

0.9

SCB13-RL-2000

2000

2440

14450

0.7

SCB13-RL-2500

2500

2880

17170

0.7

Hot Tags: SC B 13 three dimensional wound core, China, manufacturers, suppliers, factory, wholesale, buy, customized, free sample